Stratford Fireplace Installation and Operation Manual
54 _____________________________________________________________________
12. For installations where more than one chimney is located in the same non-chase or within the
same area, we suggest that their terminations be separated by at least 16" (410 mm)
horizontally, and 18" (460 mm) vertically. This separation is to prevent smoke migrating from
one chimney to another.
18"
457.21mm
18"
457.2mm
16"
406.4mm
16"
406.4mm
18"
457.2mm